How to measure
- Attic floor area: measure the floor of the vented attic, which is usually the footprint of the rooms below. Split an L-shaped house into rectangles and add them. This is not the roof area.
- Ridge vent net free area: read it off the package or data sheet, in sq in per foot. Ridge vents list about 12 to 18 sq in per foot depending on the product.
- Soffit vent net free area: read it off the package as well. Continuous soffit and eave vents commonly list 9 sq in per foot.
- Individual vents (optional): if you use box vents or roof louvers, enter the net free area printed on one vent under Advanced options.
How the attic ventilation calculation works
Required = floor area × ratio Ratio = 1/150 or 1/300 Exhaust = required ÷ 2 (ridge) Intake = required ÷ 2 (eaves) Length = area ÷ NFA per foot Count = area ÷ NFA per vent
The code sets the minimum net free ventilating area as a fraction of the vented attic floor: 1/150 normally, or 1/300 when both extra conditions are met. Net free area is the open area left after screens and louvers, which is why you use the figure printed on the product rather than the vent's size.
The area is split evenly between exhaust at the ridge and intake at the eaves, a balanced system. An even split also meets the 1/300 rule's requirement that 40 to 50 percent of the area be in upper vents.
Worked example
A 1,500 sq ft attic at the standard 1/150 ratio, with ridge vent rated 18 sq in per foot and soffit vent rated 9 sq in per foot.
- Required area: 1,500 ÷ 150 = 10 sq ft = 1,440 sq in
- Exhaust at the ridge: 1,440 ÷ 2 = 720 sq in
- Intake at the eaves: 1,440 ÷ 2 = 720 sq in
- Ridge vent: 720 ÷ 18 = 40 ft
- Soffit vent: 720 ÷ 9 = 80 ft
Buy 40 ft of ridge vent and 80 ft of soffit vent. With individual vents rated 50 sq in each, that is 15 exhaust vents and 15 intake vents.
Reading your result
The highlighted rows are what to buy: feet of ridge vent and feet of soffit vent. If the house's ridge or eaves are shorter than the result, use a vent with more net free area per foot. If the ridge is still too short, ask a roofer about a different exhaust system rather than adding roof louvers to a ridge vent: many ridge vent instructions forbid mixing exhaust types. The same goes for intake: if the eaves cannot hold a soffit vent with enough net free area per foot, ask a roofer about a compatible intake layout.
The calculator balances the system: half the area at the ridge and half at the eaves. If you change one side, change the other to match.
The reduced 1/300 ratio is only allowed under both conditions in the notes. When in doubt, use 1/150.
Assumptions
- The attic is a vented attic with an insulated floor. Unvented (conditioned) attics follow different rules.
- Half the area is exhaust at the ridge and half is intake at the eaves.
- The ratio is applied to the attic floor area. Local codes and shingle makers can ask for more.
- Vent ratings are the net free area printed on the product, so check them before you buy.
Unit conversions use exact definitions (1 in = 25.4 mm, 1 US gal = 3.785 L). See the calculation methodology for rounding rules.
When to call a professional
- Cathedral ceilings, hip roofs with a short ridge, and attics with several separate spaces need each space ventilated separately. A roofer or building department can confirm the layout and the ratio your area allows.
Frequently asked questions
How much attic ventilation do I need?
At least 1 sq ft of net free vent area for every 150 sq ft of attic floor, under IRC section R806.2. That is 10 sq ft, or 1,440 sq in, for a 1,500 sq ft attic.
When can I use the 1/300 ratio?
Only when both conditions are met: in Climate Zones 6, 7 and 8, a Class I or II vapor retarder on the warm side of the ceiling, and 40 to 50 percent of the required area in upper vents no more than 3 ft below the ridge, with the rest in the bottom third of the attic space, which in practice means the eaves or soffits. Older code editions read as 'one or both', so check which one your area uses.
What is net free area?
The open area a vent leaves for air after its screen and louvers. It is smaller than the vent's size and is printed on the package, for example 18 sq in per foot for a ridge vent or 9 sq in per foot for a continuous soffit vent.
How many feet of ridge vent do I need?
Divide half the required net free area by the vent's rating per foot. For 1,440 sq in required, that is 720 sq in at the ridge, so 40 ft of an 18 sq in per foot ridge vent.
Should insulation touch the roof?
No. The code asks for at least a 1 in air space between the insulation and the roof sheathing at the eave vents, so air can flow in. Baffles hold the insulation back.